Q2. When are continuous flammability (%LFL) monitors required to be used on heated processes?
a. Above 10% LFL
b. Above 25% LFL
c. Above 50% LFL
d. At 100% LFL
Answer: b
According to NFPA-86 “where safety ventilation rate in the oven has been designed to provide vapor concentrations between 25% and 50% of the LEL, a continuous vapor concentration high limit controller shall be provided.”
For more detailed information on NFPA 86 & LFL Read On.